Switch on a large induction motor at standstill and two things happen at once: the current surges, and the motor has to produce enough torque to break away and accelerate its load. Both effects come from the same cause — slip — and both can be estimated from the motor's per-phase equivalent circuit before anyone touches a starter or a relay setting.
Why the current is so high at standstill
An induction motor develops torque only because the rotor sees a rotating magnetic field. Slip measures how far the rotor lags that field:
s = (ns - n) / ns
where ns is synchronous speed and n is rotor speed. At standstill, n is 0, so s = 1. In the equivalent circuit, the rotor resistance appears as R2' / s, so at s = 1 that term is at its smallest, the rotor branch presents low effective impedance, and it draws substantial current. As the rotor speeds up, s falls, R2' / s grows, and the current falls toward its running value.
That is also why a single locked-rotor current multiplier is a poor substitute for a calculation. The current depends on the stator resistance and leakage reactance, the stator-referred rotor resistance and leakage reactance, and the magnetizing reactance — not just on the motor's rated current.
The equivalent circuit behind the numbers
The GridCircuits tool uses a stator-referred per-phase induction motor circuit. Its basis is stated as: "Stator-referred per-phase induction motor circuit." The formulas are:
ns = 120 f / poles; s = (ns - n) / ns; Z1 = R1 + jX1; Z2 = R2' / s + jX2'; Zm = jXm
Zparallel = Zm Z2 / (Zm + Z2); I1 = Vphase / (Z1 + Zparallel)
Vgap = Vphase - I1 Z1; I2' = Vgap / Z2; Pag = 3 |I2'|^2 R2' / s
Te = Pag / ωsync,mechanical; ωsync,mechanical = 2πns / 60; Pdeveloped = (1 - s) Pag
Use RMS phase voltage and stator-referred rotor parameters. For a wye connection, Vphase = VLL / √3 and line current equals phase current. For a balanced delta connection, Vphase = VLL and line current is √3 times phase current.
A worked example at locked rotor
Take the sample case from the calculator: a 480 V wye supply, used as 277.128 V per winding, at 60 Hz, with four poles and zero rotor speed. The illustrative circuit impedances are R1 = 0.2 Ω/phase, X1 = 0.5 Ω/phase, R2' = 0.15 Ω/phase, X2' = 0.5 Ω/phase, and Xm = 15 Ω/phase.
The calculator gives:
- Synchronous speed: 1,800 rpm
- Slip: 100%
- Stator phase current: 265.856 A RMS
- Electromagnetic torque: 158.009 N·m
- Air-gap power: 29.7841 kW
- Developed mechanical power: 0 kW
At standstill, s = 1, so Pdeveloped = (1 - s) Pag = 0 kW. No mechanical power is developed yet because nothing is moving, even though 29.7841 kW crosses the air gap. That power is dissipated as rotor copper loss at locked rotor, while the 158.009 N·m of electromagnetic torque is what is available to start the load moving.
For a wye motor, the 265.856 A phase current is also the line current. That is an RMS phase current from the steady equivalent circuit, not the first asymmetrical peak after switching.
What changes as the motor speeds up
Increase the rotor speed toward 1,800 rpm and slip falls, R2' / s rises, stator current falls, and developed mechanical power, (1 - s) Pag, becomes nonzero. Running the same circuit at several speeds is a quick way to see whether the available torque stays above the load torque through the whole acceleration, rather than checking only the locked-rotor point. For a real motor, use nameplate and manufacturer test data, not the illustrative impedances in this example.
Practical checks before you set anything
Treat the result as a preliminary-design and education estimate, and verify it against the motor nameplate, test data, and the manufacturer's data before final design. The model is a balanced sinusoidal steady equivalent circuit with constant parameters; core-loss resistance is omitted and mechanical losses are excluded, so developed torque and power differ from shaft output.
Starting protection must still allow the actual acceleration time while respecting hot and cold thermal withstand and locked-rotor limits. As the calculator notes, a current multiplier alone does not establish an appropriate relay setting.
Try it with your own motor data
Replace the illustrative impedances with your motor's test values, enter the phase voltage for your connection, and step the rotor speed from zero toward synchronous speed to get the stator current, slip, air-gap power, and electromagnetic torque at each point.
Try it here: Induction Motor Starting Current & Torque Calculator