10BASE-T1L brings Ethernet to field devices over a single twisted pair. The point-to-point link carries 10 Mbit/s in each direction and can reach 1 km over a channel that meets the specification. The same pair can power the field device when the ports at both ends support the selected power profile. [1] [3]
How both ends transmit on the same pair
10BASE-T1L is the long-reach, 10 Mbit/s variant of Single Pair Ethernet (SPE). Clause 146 of IEEE 802.3, introduced by amendment 802.3cg, defines its physical layer, or PHY. Ethernet frames retain their format. The encoding and electrical characteristics of the link change. [1] [2]
4B3T encoding represents each group of four bits with three ternary symbols. PAM-3 modulation assigns each symbol one of three differential voltage levels, which the receiver reads across the two conductors. This translates to 7.5 million symbols per second for a bit rate of 10 Mbit/s. The encoding keeps the signal balanced over time, which allows AC coupling in the data path. [2] [3]
Both transceivers can send at the same time. At either end, the receiver sees the incoming signal combined with the one its own transmitter puts on the wire. The transceiver uses its transmitted symbols to estimate and subtract the local echo. This echo cancellation lets the receiver distinguish the far-end signal even after attenuation over the cable. [2] [4]
100BASE-TX, commonly associated with RJ45 ports, uses two pairs, one for each direction. Its electrical signalling differs from 10BASE-T1L. Joining the segments requires a switch with ports for both physical layers or an active media converter. Topologies also vary within Single Pair Ethernet. 10BASE-T1S serves short links and supports a shared bus. Each 10BASE-T1L link connects two ports. [2] [5]
What determines whether a link can reach 1 km
The 1 km reach applies in 2.4 V peak-to-peak mode, with a channel that meets the electrical limits. When auto-negotiation is enabled, the PHYs use this level if both advertise support and at least one requests it. The baseline 1.0 V peak-to-peak mode has a tighter channel attenuation limit. [4] [6]
Insertion loss measures how much signal is lost through the channel and varies with frequency. Return loss describes reflections caused by impedance discontinuities at splices and connectors. A higher return loss in decibels corresponds to a weaker reflection. Pair balance matters too. If the conductors respond differently to common-mode interference, some of it appears at the receiver as a differential signal. To qualify existing cabling, compare the losses of the entire channel, including splices, with the specified curves from 100 kHz to 20 MHz. Return loss is referenced to a differential impedance of 100 Ω. [6]
Connecting a field device with an SPI MAC-PHY
The MAC handles Ethernet frames. The PHY converts the data it receives from the MAC into electrical signals on the line. A microcontroller with an Ethernet MAC can connect to a 10BASE-T1L PHY through an interface such as RMII. A MAC-PHY such as the ADIN1110 combines both blocks and exchanges frames and commands with the processor over SPI. This lets microcontrollers without a built-in Ethernet MAC use the link. On the line side, the ADIN1110 uses an external hybrid circuit to couple its separate transmit and receive pins to the same pair. [4]
Microcontroller
⇅ SPI
10BASE-T1L MAC-PHY
⇅
Coupling circuit
⇅
Twisted pair
⇅
10BASE-T1L switch port
The microcontroller exchanges Ethernet frames over SPI. The coupling circuit transfers the PHY signal to the twisted pair. [4]
In firmware, the driver configures the MAC-PHY and moves frames through its transmit and receive queues. The ADIN1110 supports an SPI clock of up to 25 MHz. Effective throughput also depends on SPI protocol overhead, buffer sizes and how quickly the microcontroller services interrupts and drains the queues. With Modbus TCP, the microcontroller also runs the TCP/IP stack and the application that makes the data available. [4] [8]
10BASE-T1L and RS-485 compared
RS-485 specifies the electrical characteristics of transmitters and receivers. On a two-wire bus, nodes take turns transmitting. The trunk has a termination at each end, and the stubs are kept short. In the Modbus serial line specification, “two-wire” refers to the two signal conductors. A third conductor provides a common reference. RTU is the binary message format for the serial line. Modbus TCP carries the Modbus application functions over TCP/IP with a different header. [7] [8]
Interface characteristics for field instruments
| Characteristic | 10BASE-T1L | Two-wire RS-485 |
|---|---|---|
| Topology | One pair per point-to-point link. Switches aggregate multiple links. | One signal pair shared by multiple devices on the same bus. |
| Duplex | Simultaneous transmission in both directions. | Nodes take turns transmitting on the shared pair. |
| Data rate and reach | 10 Mbit/s per direction. Up to 1 km at 2.4 V peak-to-peak with a compliant channel. [6] | Reach depends on data rate and cabling. TI's design guide cites approximately 1,200 m at 100 kbit/s as a reference. [7] |
| Device firmware | Ethernet driver, a network stack suited to the chosen protocol, and application logic. | UART, transceiver direction control, and a serial protocol. |
When many instruments exchange only a few values, a Modbus TCP/RTU gateway can bring the serial trunk onto the IP network. The gateway translates requests, and the instruments continue to share the bus polling cycle. 10BASE-T1L is worth considering when individual instruments need to be reachable over Ethernet for readings, configuration or diagnostics. The choice affects the number of active ports, cable routes and device firmware. [1] [7] [8]
Data and power on the same pair
PoDL (Power over Data Lines) defines power delivery over a single pair. Industrial SPoE (Single-Pair Power over Ethernet) classes 10 through 15 set limits for voltage, current, power and maximum cable resistance. The supplying 10BASE-T1L port acts as the power sourcing equipment (PSE). The field instrument is the powered device (PD). The two ports need compatible power classes. Inductors in the power path pass direct current while impeding the data signal. The PHY receives the signal through an AC-coupled path. At the field device, the PD controller manages startup and the DC/DC converter supplies the electronics. [3]
Data reach depends on channel loss at the signalling frequencies. Power delivery depends on cable resistance and the load. The voltage drop along the cable is the current multiplied by the loop resistance, the combined resistance of the outgoing and return conductors. Cable power losses rise with the square of the current. Choosing a power class means accounting for the minimum supply voltage, conductor temperature, DC/DC efficiency and startup current. [3]
When the field electronics require galvanic isolation from the line, the isolation barrier must account for both paths. Analog Devices' CN0575 reference design uses a transformer for the data path and an isolated DC/DC converter for power. The choice and sizing of the coupling components also affect signal integrity. [3]
What Ethernet-APL adds
Ethernet-APL uses 10BASE-T1L and defines port profiles for process automation, including intrinsically safe installations. In a topology with field switches, the trunk can reach 1,000 m and the spur to an instrument can reach 200 m, depending on the port profile and cabling. APL profiles define signal and power compatibility between ports. Intrinsically safe profiles also set limits for interconnecting ports in hazardous areas. [6] [9]
Assessing timing and link stability
The 10 Mbit/s figure is the line rate. Headers and interframe gaps also affect application throughput. Time from acquisition to an updated value at the PLC includes transmission and propagation along the cable, forwarding through switches, microcontroller queues and the polling cycle. For a control function, specify two deadlines. One is the maximum time for a new reading to reach the PLC. The other is how soon the PLC must mark a reading as stale after communication is lost. [1] [6]
During system qualification, signal-quality indicators help track link performance under electrical interference. Reflectometry available on devices such as the ADIN1110 helps locate possible cable discontinuities. For a powered link, verify the minimum voltage at startup as well. After a link interruption, application-level recovery is complete when the PLC receives a fresh, valid sample. [3] [10]
References
- IEEE, amendment 802.3cg and IEEE 802.3 standard, Clause 146.
- IEEE 802.3cg Task Force, tutorial on 10 Mbit/s Single Pair Ethernet.
- Analog Devices, CN0575 reference design.
- Analog Devices, ADIN1110 data sheet and technical article on connecting a MAC-PHY over SPI.
- Cisco, 100BASE-TX cabling specifications.
- Analog Devices, 10BASE-T1L reach and channel requirements. Texas Instruments, 10BASE-T1L channel design note.
- Texas Instruments, The RS-485 Design Guide.
- Modbus Organization, Modbus over serial line specification and Modbus TCP/IP messaging guide.
- IEC, IEC TS 63444 specification for Ethernet-APL and Ethernet-SPE profiles. Ethernet-APL, FAQ on trunks and spurs.
- Analog Devices, AN-2553 on link and cable diagnostics.