Fiber reach by optic speed: how far 10G, 25G, 100G, and 400G actually go

Fiber reach by optic speed: how far 10G, 25G, 100G, and 400G actually go

The most common optic mistake on the floor is not a dirty face or a bad splice. It is an optic specced for a shorter run than the plant it is plugged into. The link worked at 10G for years, the run gets upgraded to 100G, the new optic goes in, and the link never comes up — or comes up and flaps under load. Nothing is broken. The fiber did not change, the connectors did not change, and the optic is not faulty. The speed changed, and with it the distance that same fiber can carry.

Reach is not a property of the fiber alone or the optic alone. It is the pair, at that speed, at that wavelength, on that fiber type. This is the table I check before I install.

The reach table

Distances are the standard spec figures for the optic type — the optic's own datasheet is authoritative and wins over this table whenever they disagree. SR means short reach on multimode at 850 nm. LR and ER are long reach on single-mode. DR is the 500-metre single-mode parallel optic. Where two figures are given, the first is OM3 and the second is OM4.

  • 10G, 10GBASE-SR, OM3 / OM4: 300 m / 400 m
  • 10G, 10GBASE-LRM, OM1 / OM2: 220 m
  • 10G, 10GBASE-LR, single-mode: 10 km
  • 10G, 10GBASE-ER, single-mode: 40 km
  • 25G, 25GBASE-SR, OM3 / OM4: 100 m / 150 m
  • 25G, 25GBASE-LR, single-mode: 10 km
  • 25G, 25GBASE-ER, single-mode: 30 km
  • 100G, 100GBASE-SR4, OM3 / OM4: 100 m / 150 m
  • 100G, 100GBASE-SWDM4, OM3 / OM4: 75 m / 100 m
  • 100G, 100GBASE-DR, single-mode: 500 m
  • 100G, 100GBASE-LR4, single-mode: 10 km
  • 100G, 100GBASE-ER4, single-mode: 40 km
  • 400G, 400GBASE-SR8, OM3 / OM4: 100 m / 150 m
  • 400G, 400GBASE-DR4, single-mode: 500 m
  • 400G, 400GBASE-FR4, single-mode: 2 km
  • 400G, 400GBASE-LR4, single-mode: 10 km
  • 400G, 400GBASE-ER8, single-mode: 40 km

Read the table sideways and the pattern jumps out: every time the speed doubles, the multimode reach roughly halves. 10G-SR does 300 metres on OM3; 25G-SR does 100; 100G-SR4 does 100; 400G-SR8 does 100. That is why the plant that was generous at 10G is marginal at 100G and out of spec at 400G.

Single-mode is the opposite story: LR is 10 km at 10G, 25G, 100G, and 400G alike, because single-mode has no modal dispersion to eat the budget. When a run is long, single-mode is the answer; when it is short, multimode is cheaper and the table tells you whether it is short enough.

Why the same fiber reaches further at a lower speed

On multimode, the limit is modal dispersion: light takes many paths down a 50-micron core, the paths arrive at different times, and at higher speeds the spread blurs one bit into the next. The fiber's modal bandwidth — 2,000 MHz·km for OM3, 4,700 MHz·km for OM4 at 850 nm — is the budget, and the speed spends it. That is why OM4 reaches further than OM3 at the same speed, and why the same OM3 run carries 10G three times further than 100G.

On single-mode there is only one path, so there is no modal dispersion and the limit becomes the loss budget instead: the optic's transmit power minus the receiver's sensitivity, spent on fiber attenuation and connector and splice loss. The third factor is the lane count: SR4, DR4, and SR8 are parallel optics, four or eight lanes at once, and every lane has to arrive clean — one bad lane fails the whole link, which is why a dirty MPO face takes down a 100G link that would have survived as four separate 25G links.

How a reach mismatch shows up

It shows up in three ways, and only the first one is obvious. First, the link never comes up: no light at the far end, or light so weak the receiver cannot lock. Second, the link comes up and then flaps or throws CRC and framing errors under load — the signal is just good enough at idle and just bad enough at line rate, which is the hardest version to catch because it passes a quick check and fails in production. Third, the link looks fine until you check the DOM readings and find the received power sitting at the bottom of the budget with no margin left — a link that works today and fails the next time someone re-patches it or the temperature shifts.

The trap in all three is the same: the instinct is to clean the faces, swap the patch cord, or replace the optic with another one of the same type. None of those change the reach. If the run is longer than the optic's spec distance, the only fixes are the right optic for the distance, a shorter path, or a different fiber type — and the cheapest time to find that out is before the install, not after the ticket escalates.

Checking the match before you install

The check takes two minutes and has four steps. First, know the run: measure it, or read the plant record — the as-built length, not the estimate. If nobody knows the length, the OTDR gives it. Second, read the optic code: SR, SR4, LR, ER, DR, FR — printed on the optic or in the switch's transceiver inventory — and match it against the table for the fiber type in the plant. OM3 or OM4 matters as much as the optic code: SR4 on OM3 is 100 metres, on OM4 is 150.

Third, run the loss budget: fiber length times attenuation, plus connector and splice loss, against the optic's budget. Fourth, after the install, measure: a light source and power meter test on the run and a DOM reading on the optic, both recorded. If the measured loss is inside budget and the DOM received power has margin, the reach is proven, not assumed.

Recording the reach in the ticket

The optic and the run length belong in the ticket, because the next person on the link needs to know what distance this link was built for — otherwise they will re-clean faces that are already clean and re-test an optic that was never the problem. The minimum useful line:

  • Run length and fiber type
  • Optic type and its spec reach
  • Measured loss against the budget
  • DOM received power
  • The cleaning evidence — inspected, cleaned, inspected

Five fields, and the next tech knows the link was built inside its reach with margin to spare — which is the information that stops the same optic from being blamed twice. If the run is near the limit, say so: "run 140 m, SR4 limit 150 m on OM4, 10 m margin" is a warning the next person will thank you for.

A question for you

What is the longest run you have seen a short-reach optic asked to cover — and did the link fail outright, or fail slowly under load?